Sentry 750 Command Center 2 pump
Time, Filter, Cooler, Warmer buttons not working.
Jets, Air, and Light buttons normal.
Spa heats to 79 degrees but we can not adjust temp up from that.
Sentry 750 Command Center 2 pump
Time, Filter, Cooler, Warmer buttons not working.
Jets, Air, and Light buttons normal.
Spa heats to 79 degrees but we can not adjust temp up from that.
5 thoughts on “Sentry 750 Command Center”
Tim check the cable from the topside control down to the PWA connection for breaks. If you don’t see any breaks in the cable and the led status doesn’t change when you press the up or down for temperature you could have a bad topside control panel. Send us the serial number for your spa if you would like a purchase link for a new topside control panel.
The serial number can be found on the id sticker near the Sentry Control Box.
Nigel,
I carefully used my Dremel th get through the acrylic and I have continuity between the end of the cord all the way to the control panel topside.
S/N OCL3600-CL311702-0398
Thank you for your help,
Tim
Tim when you press the warmer button does the temperature number Led on the control panel go up and when you press the cooler button does the temperature number Led go down? Or does the Led number on the control panel stay constant/locked at 79 at all times no mattter what button you press?
It stays locked at 79 at all times no matter what button I press
Tim you could have a bad topside control there. Would you like us to send you a purchase link?